Skip to main navigation Skip to search Skip to main content

A study on high-current rectifier systems with mitigated time-varying magnetic field generation at AC input and DC output busbars

  • Yongsug Suh*
  • , Changwoo Kim
  • *Corresponding author for this work
  • Jeonbuk National University

Research output: Contribution to journal › Journal article › peer-review

Abstract

This paper investigates occupational exposure to time-varying magnetic field generation in high-power rectifier systems. Two different kinds of high-power rectifier systems rated for 25kA are modeled and analyzed. The performance is compared and evaluated on the basis of exposure guidelines from the International Commission on Non-Ionizing Radiation Protection (ICNIRP). In order to focus on the qualitative effect of rectifier operation, the mechanical structure of the current-carrying conductors is simplified as an infinite long busbar model and low-frequency harmonic contents up to 65kHz are considered. A thyristor rectifier generates a significant amount of low-frequency magnetic field harmonic contents, both at the ac and dc sides of the rectifier, infringing the limit from ICNIRP. The multilevel IGCT-type rectifier has almost negligible field generation from the ac input side and smaller harmonic contents in the dc load side, complying with ICNIRP guidelines. This remarkable advantage of multilevel rectifier-IGCT type can lead to a simpler site layout design for installation and cost-effective compliance to the guidelines of occupational exposure against the magnetic field.

Original languageEnglish
Article number6017131
Pages (from-to)1212-1219
Number of pages8
JournalIEEE Transactions on Power Electronics
Volume27
Issue number3
DOIs
StatePublished - 2012

Keywords

  • EMI
  • high-power rectifier
  • ICNIRP guideline
  • time-varying magnetic field

Quacquarelli Symonds(QS) Subject Topics

  • Engineering - Electrical & Electronic
  • Engineering - Petroleum

Fingerprint

Dive into the research topics of 'A study on high-current rectifier systems with mitigated time-varying magnetic field generation at AC input and DC output busbars'. Together they form a unique fingerprint.