In a single-phase grid-tied inverter, the direct current (DC) offset error included in the measured grid side phase current has various causes, such as a non-ideal current sensor, unbalanced power supply of an operational amplifier, and nonlinear features of analog components in interface circuits, etc. If the DC offset error is included in the measured current, it causes the secondary harmonic of fundamental frequency and the DC component in grid phase current which result in degradation of inverter performance. In this paper, a theoretical detection method of the secondary harmonic of the fundamental frequency and a DC component in grid phase current for a proportional-resonant (PR) current control system is introduced. Based on the detection method, an algorithm for compensating DC offset error is also presented for single-phase grid-tied inverters. Simulation results and experimental verification of the DC offset error compensation algorithm are shown in this paper.

Original languageEnglish
Article number2308
JournalEnergies
Volume11
Issue number9
DOIs
StatePublished - 2018.09

Keywords

  • DC component
  • Direct current (DC) offset error
  • Proportional-resonant (PR) current control
  • Secondary harmonic component
  • Single-phase grid-tied inverter

Quacquarelli Symonds(QS) Subject Topics

  • Mathematics
  • Engineering - Electrical & Electronic
  • Engineering - Petroleum

Fingerprint

Dive into the research topics of 'DC offset error compensation algorithm for PR current controlofa single-phase grid-tied inverter'. Together they form a unique fingerprint.

Cite this