Energy consumption characteristics of an absorption chiller during the partial load operation

  • Chan Woo Park
  • , Jin Hee Jeong
  • , Yong Tae Kang*
  • *Corresponding author for this work
  • LG Corporation
  • Kyung Hee University

Research output: Contribution to journalJournal articlepeer-review

Abstract

The objectives of this study are to analyze performance characteristics during partial load operation and to calculate energy consumption amount of H2O/LiBr absorption chiller with a capacity of 210 RT. The effect of cooling water flow rate and cooling water inlet temperature on the absorption performance and energy saving is quantified during the partial load operation. It is found that the performance of absorption system is more sensitive to the change of inlet water temperature rather than the cooling water flow rate. Even if the cooling water flow rate is reduced to 60% of the standard value, the capacity is recovered if the temperature of cooling water decreases about 2.0°C. The pumping power of cooling water is 4 times higher than that of cooling tower during the partial operation mode and the pumping power of cooling water becomes more significant with decreasing the partial load. It is concluded that when the partial load is in the range of 100-40%, the reduction of the required power by 23% can be realized by decreasing the cooling water inlet temperature of 1.0°C.

Original languageEnglish
Pages (from-to)948-954
Number of pages7
JournalInternational Journal of Refrigeration
Volume27
Issue number8
DOIs
StatePublished - 2004.12

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • Absorption system
  • Capacity reduction
  • Energy consumption
  • Experiment
  • Measurement
  • Water-lithium bromide

Fingerprint

Dive into the research topics of 'Energy consumption characteristics of an absorption chiller during the partial load operation'. Together they form a unique fingerprint.

Cite this