Skip to main navigation Skip to search Skip to main content

Fluxgate DC 센서를 이용한 직류 누전차단기의 동작 성능 안정화에 관한 연구

Translated title of the contribution: Study on the Stabilization of Operating Performance of DC Earth Leakage Breaker Using Fluxgate DC Sensor
  • Ki Yeon Lee
  • , Seung Taek Lim
  • , Chan Hyeok Oh
  • , In Ho Ryu*
  • , Jung Soo Park
  • *Corresponding author for this work
  • Korea Electrical Safety Corporation
  • DaeRyuk Co. Ltd.

Research output: Contribution to journalJournal articlepeer-review

Abstract

In recent years, the need to use DC power distribution systems has increased and there has been a growing public interest in ensuring their safety. In particular, residual current devices (RCDs) are recognised as an important piece of protective equipment for users, preventing not only equipment accidents but also personal accidents. Therefore, it is necessary to verify the operation of DC RCDs in advance. Therefore, this paper investigates a stable sensor data processing method and algorithm of DC RCDs to ensure the safety of DC electrical equipment and protect people from electric shock. DC RCDs use a fluxgate current sensor as the DC ZCT, but as the fault current increases, the pulse generation frequency increases and distortion occurs. In addition, when the fault current is such that the core is saturated, the pulse generation is interrupted and the fault current is not detected and the breaker does not operate. To solve these problems, a data processing technique has been used which applies compensation by frequency analysis of the magnetic excitation circuit of the sensor to stabilize the operating performance of the protection device. The DC RCD developed in this paper can be used as a protective device to ensure the safety of DC equipment and to protect people from electric shock, and it is judged that it will contribute to ensuring electrical safety by ensuring safety in the event of a fault and taking appropriate preventive measures by confirming the exact cause of the operation of the protective device.

Translated title of the contributionStudy on the Stabilization of Operating Performance of DC Earth Leakage Breaker Using Fluxgate DC Sensor
Original languageKorean
Pages (from-to)2085-2090
Number of pages6
JournalTransactions of the Korean Institute of Electrical Engineers
Volume73
Issue number11
DOIs
StatePublished - 2024.11

Keywords

  • DC distribution
  • DC earth leakage breaker
  • Electrical safety
  • Fluxgate sensor
  • Over-current leakage

Quacquarelli Symonds(QS) Subject Topics

  • Engineering - Electrical & Electronic
  • Engineering - Petroleum

Fingerprint

Dive into the research topics of 'Study on the Stabilization of Operating Performance of DC Earth Leakage Breaker Using Fluxgate DC Sensor'. Together they form a unique fingerprint.