Abstract
An ignition experiment was conducted with a cross-linked polyethylene insulated tray flame-retardant polyvinyl chloride sheathed cable by generating a 100 W direct current arc. The experiments generated a series arc by applying the UL 1699B revised standard and measuring arcing current, arcing voltage, etc. The reliability analysis was conducted using a statistical program on arc duration time and energy obtained through the measured data. The confidence level of the probability distribution diagram and cumulative density function was within 95%, and the time and arc energy corresponding to 5% ignition probability was 2.38 s and 255 J, respectively. As for the 6% ignition probability, the ignition time was 2.64 s, exceeding the 2.5 s UL 1699B conformity standard. The time and arc energy corresponding to 50% ignition probability was 9.38 s and 697 J, respectively, indicating that the ignition probability within 10 s and 700 J was more than 50%. This study concluded that the conformity standard time in UL 1699B needs to be lower than 2.5 s for 100 W-level direct current arc generation tests based on the analysis results.
| Original language | English |
|---|---|
| Pages (from-to) | 3593-3599 |
| Number of pages | 7 |
| Journal | Journal of Electrical Engineering and Technology |
| Volume | 17 |
| Issue number | 6 |
| DOIs | |
| State | Published - 2022.11 |
Keywords
- DC arc
- Ignition probability
- Reliability analysis
- TFT-CV cable
- UL1699B
Quacquarelli Symonds(QS) Subject Topics
- Engineering - Electrical & Electronic
- Engineering - Petroleum
Fingerprint
Dive into the research topics of 'Statistical Analysis of Ignition Time and Energy of the TFR-CV Cable Ignition Experiments Using 100 W DC Arc'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver